Building Code Modifications
Overview
These are the requests for modifications considered in 2019:
FILE # | DATE RECEIVED | STATUS | DATE MAILED | PROPERTY LOCATION | TOWN | CODE SECTION(s) | CODE DEFINITION |
M-0358-19 | 5/31/19 | APPROVED | 6/5/19 | 282 Broad Brook Road | Enfield | R311.7.2 | Section R311.7.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0357-19 | 5/31/19 | APPROVED | 6/5/19 | 145 Columbus Blvd. | New Britain | 3006 | Section 3006, of the 2015 International Building Code portion of the 2018 State Building Code. |
M-0356-19 | 5/31/19 | APPROVED | 6/3/19 | 9 Green Valley Lake Road | East Lyme | 1999SBC | continue to utilize the provisions of the 1999 State Building Code in which the addition with construction under for the remaining inspections. |
M-0355-19 | 5/31/19 | APPROVED | 6/3/19 | 860 Orange Avenue | West Haven | 1027.5 | Section 1207.5, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “Exterior exit stairways shall have a minimum fire separation distance of 10 feet to adjacent lot lines”. |
M-0354-19 | 5/31/19 | APPROVED | 6/3/19 | 155 Nearwater Lane | Darien | 1609.3 | Section 1609.3, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “The ultimate design wind speed for the determination of the wind loads shall be determined by Appendix N”. |
M-0353-19 | 5/31/19 | APPROVED | 6/3/19 | 330 Park Avenue | Bloomfield | 1024.6.1 | Section 1024.6.1, of the 2012 International Building Code portion of the 2016 State Building Code, which sets forth requirements for “Egress path marking systems within exit access corridors”. |
M-0352-19 | 5/30/19 | APPROVED | 6/3/19 | 369 Pine Street | Middletown | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0351-19C | 5/30/19 | APPROVED | 6/3/19 | 6 Island Hill Avenue | Ridgefield | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0351-19B | 5/30/19 | APPROVED | 6/3/19 | 6 Island Hill Avenue | Ridgefield | R302.11 | Section R302.11, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for “fire blocking”. |
M-0351-19A | 5/30/19 | APPROVED | 6/3/19 | 6 Island Hill Avenue | Ridgefield | R311.7.2 | Section R311.7.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0350-19C | 5/30/19 | APPROVED | 6/3/19 | 138 Mimosa Circle | Ridgefield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0350-19B | 5/30/19 | APPROVED | 6/3/19 | 138 Mimosa Circle | Ridgefield | R302.11 | Section R302.11, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for “fire blocking”. |
M-0350-19A | 5/30/19 | APPROVED | 6/3/19 | 138 Mimosa Circle | Ridgefield | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0349-19 | 5/29/19 | APPROVED | 5/31/19 | 665 Wetherell Street | Manchester | 2016SBC | Continued use of the 2016 State Building Code |
M-0348-19 | 5/29/19 | APPROVED | 6/3/19 | 74 Christie Hill Road | Darien | 1609.3 | Section 1609.3, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “The ultimate design wind speed for the determination of the wind loads shall be determined by Appendix N”. |
M-0347-19 | 5/29/19 | APPROVED | 5/31/19 | 113 Hamilton Street | Meriden | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0346-19 | 5/29/19 | APPROVED | 5/31/19 | 45 Butternut Hollow Road | Greenwich | 2016SBC | Continued use of the 2016 State Building Code |
M-0345-19 | 5/29/19 | APPROVED | 5/31/19 | 46 Fernwood Lane | Wilton | 2016SBC | Continued use of the 2016 State Building Code |
M-0344-19 | 5/28/19 | APPROVED | 5/31/19 | 21 Van Dyke Avenue | Hartford | 1013.3 | Section 1013.3, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “Required guards shall not be less than 42 inches high along stairs”. |
M-0343-19 | 5/28/19 | APPROVED | 5/31/19 | 250 Stoneliegh Square | Fairfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0342-19 | 5/24/19 | APPROVED | 5/31/19 | 310 Cherry Lane | Oakdale | 2016SBC | Continued use of the 2016 State Building Code |
M-0341-19 | 5/24/19 | APPROVED | 5/31/19 | 58 St. Nicholas Road | Darien | 3901.4.1 | |
M-0340-19 | 5/24/19 | APPROVED | 5/31/19 | 22 Candlewood Heights | New Milford | R405.1 | |
M-0339-19 | 5/23/19 | APPROVED | 6/3/19 | 12 Norfolk Road | Litchfield | 10101.9; 10101.9.9; 1016.2 | Sections 10101.9; 10101.9.9; 1016.2, of the 2015 International Building Code portion of the 2018 State Building Code, which sets forth requirements for “Egress and locking arrangements for egress doors”. |
M-0338-19 | 5/23/19 | DENIED | 5/31/19 | 630 Steamboat Road, Apt 4CN | Greenwich | 1023.5 | Section 1023.5, of the 2015 International Building Code portion of the 2018 State Building Code, which states that “Penetrations into or through interior exit stairways are prohibited except for equipment and ductwork necessary for independent ventilation or pressurization, sprinkler piping, standpipes, electrical raceway for fire department communication and security systems and electrical raceway serving the interior exit stairway”. |
M-0337-19 | 5/23/19 | APPROVED | 5/31/19 | 3 Pleasant View Road | New Milford | 2016SBC | Continued use of the 2016 State Building Code |
M-0336-19 | 5/16/19 | APPROVED | 5/31/19 | 60 Liberty Street | Pawcatuck | 1014.6 | Section 1014.6, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “At locations where handrails are not continuous between stairway flights, including the top and bottom of a stairway, the handrails shall extend horizontally at least 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser”. |
M-0335-19 | 5/13/19 | DENIED | 5/31/19 | 58 St. Nicholas Road | Darien | 3901.2.1 | Section 3901.2.1, of the 2012 International Residential Code portion of the 2016 State Building Code, which states that “A receptacle outlet shall be installed so that no point along the wall line is more than 6 feet from a receptacle outlet”. |
M-0334-19 | 5/24/19 | APPROVED | 5/31/19 | 21 Van Dyke Avenue | Hartford | 715.1 | Section 715.1 of the 2015 International Plumbing code portion of the 2018 State Building code which states in part, that “Plumbing fixtures installed on a floor with a finished floor elevation above the elevation of the manhole cover of the next upstream manhole in the public sewer shall not discharge through a backwater valve”. |
M-0333-19 | 5/22/19 | APPROVED | 5/31/19 | 88 Bassett Road | North Haven | 506.2 | Section 503.2 of the 2015 International Building code portion of the 2018 State Building code which states in part, that “The areas of all buildings shall be determined in accordance with the applicable provision of this section”. |
M-0332-19 | 5/22/19 | APPROVED | 5/28/19 | 34 Inwood Road | Trumbull | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0331-19 | 5/22/19 | APPROVED | 5/28/19 | 531 Route 12 | Groton | 903.2.9.1 | |
M-0330-19 | 5/22/19 | APPROVED | 5/31/19 | 39 Foxboro Road | Essex | R326.6.1 | |
M-0329-19 | 5/21/19 | w/DAN | 75 Eastern Point Road | Groton | |||
M-0328-19 | 5/21/19 | APPROVED | 5/28/19 | 156 Nunzio Drive | Plantsville | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0327-19 | 5/21/19 | APPROVED | 5/28/19 | 90 Naugatuck Avenue | Milford | 1026.5 | Section 1026.5, of the 2012 International Building Code portion of the 2016 State Building Code, which states that “Exterior exit ramps shall have a minimum fire separation distance of 10 feet to adjacent lot lines”. |
M-0326-19 | 5/21/19 | APPROVED | 5/28/19 | 47 Sea Spray Avenue | Niantic | R301.2.1.2 | |
M-0325-19 | 5/23/19 | APPROVED | 5/31/19 | 72 Industrial Drive | Southington | 403.1 | |
M-0324-19 | 5/20/19 | APPROVED | 5/28/19 | 24 Thompson Road | East Windsor | C503.3.1 | |
M-0323-19 | 5/20/19 | APPROVED | 5/28/19 | 19 Pleasant Rise Circle | Brookfield | 407.13.2.1.1 | |
M-0322-19B | 5/20/19 | APPROVED | 5/28/19 | 161 Main Street | Wethersfield | 1208.2 | |
M-0322-19A | 5/20/19 | APPROVED | 5/28/19 | 161 Main Street | Wethersfield | 1011.2 | Section 1011.2, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “The width of stairways shall be not less 44 inches”. |
M-0321-19 | 5/20/19 | APPROVED | 5/28/19 | 3 Ina's Drive | Brookfield | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0320-19 | 5/20/19 | APPROVED | 5/28/19 | 75 Eastern Point Road | Groton | 2902.1 | Section 2902.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 2902.1 (Drinking Fountain and Sink Required)” |
M-0319-19 | 5/16/19 | APPROVED | 5/28/19 | 23 Carroll Ct | Naugatuck | R317.1.3 | |
M-0318-19 | 5/16/19 | APPROVED | 5/20/19 | 8 Mountain Wood Drive | Greenwich | R311.7.2 | Section R311.7.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0317-19 | 5/16/19 | APPROVED | 5/20/19 | 10 Rabbit Lane | Brookfield | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0316-19 | 5/16/19 | APPROVED | 5/20/19 | 270 Mohegan Avenue | New London | 707.3.2; C402.1.3 | |
M-0315-19 | 5/16/19 | APPROVED | 5/20/19 | 340 Boston Post Road | Madison | ACE/SE1 7-16 | |
M-0314-19 | 5/16/19 | APPROVED | 5/20/19 | 191 Summer Street | Stamford | 1022.4 | |
M-0313-19B | 5/15/19 | APPROVED | 5/20/19 | 679 Ridgebury Road | Ridgefield | R302.11 | Section R302.11, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for “fire blocking”. |
M-0313-19A | 5/15/19 | APPROVED | 5/20/19 | 679 Ridgebury Road | Ridgefield | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0312-19 | 5/15/19 | APPROVED | 5/20/19 | 310 Copper Ridge | Southington | 602.10 | |
M-0311-19B | 5/15/19 | APPROVED | 5/20/19 | 1798 State Street | Hamden | R305.1 | Section R305.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Habitable rooms and hallways shall have a ceiling height of not less than 7 feet”. |
M-0311-19A | 5/15/19 | APPROVED | 5/20/19 | 1798 State Street | Hamden | R305.1 | Section R305.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Habitable rooms and hallways shall have a ceiling height of not less than 7 feet”. |
M-0310-19 | 5/15/19 | APPROVED | 5/15/19 | 26 Prospect Mountain Road | Salisbury | R311.7.12; R311.7.12.1; R311.7.12.2 | |
M-0309-19 | 5/14/19 | APPROVED | 5/15/19 | 330 Park Road | Bloomfield | 1109.2.4 | utilize the “Faucets and Controls Requirements”, of the 2015 International Building Code. |
M-0308-19 | 5/14/19 | APPROVED | 5/15/19 | 7 Mayfair Lane | Westport | R403.1 | |
M-0307-19 | 5/14/19 | APPROVED | 5/15/19 | 10 Queen Street | Enfield | R305.1 | Section R305.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Habitable rooms and hallways shall have a ceiling height of not less than 7 feet”. |
M-0306-19R | 5/23/19 | DENIED | 5/31/19 | REVISED-75 View Street | Greenwich | R311.6.2 | |
M-0306-19 | 5/13/19 | APPROVED | 5/15/19 | 75 View Street | Greenwich | R311.6.2 | |
M-0305-19 | 5/3/19 | DENIED | 5/15/19 | 65 Tokeneke Road | Darien | 410.4 | Section 410.4, of the 2015 International Building Code portion of the 2018 State Building Code, which states that “Permanent platforms shall be constructed of materials as required for the type of construction of the building in which the permanent platform is located. Permanent platforms are permitted to be constructed of fire-retardant-treated wood for Types I, II and IV construction where the platforms are not more than 30 inches (762 mm) above the main floor, and not more than 3,000 square feet (279 m2) in area”. |
M-0304-19 | 5/10/19 | APPROVED | 5/14/19 | 512 Middlesex Road | Darien | 1609.3 | Section 1609.3, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “The ultimate design wind speed for the determination of the wind loads shall be determined by Appendix N”. |
M-0303-19B | 5/10/19 | APPROVED | 5/14/19 | 290-292 Windsor Street | Windsor | 1014.6 | Section 1014.6, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “At locations where handrails are not continuous between stairway flights, including the top and bottom of a stairway, the handrails shall extend horizontally at least 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser”. |
M-0303-19A | 5/10/19 | APPROVED | 5/14/19 | 290-292 Windsor Street | Windsor | 1011.6 | Section 1011.6, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “Every landing shall have a minimum dimension of 36 inches”. |
M-0302-19 | 5/10/19 | APPROVED | 5/14/19 | 1160 Silas Dean Highway | Wethersfield | 240.24(D) | Section 240.24(D), of the 2017 National Electrical Code portion of the 2018 State Building Code, which states in part that “Overcurrent devices shall not be located in clothes closets”. |
M-0301-19B | 5/10/19 | APPROVED | 5/13/19 | 119 Mimosa Cir | Ridgefield | R302.11 | Section R302.11, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for “fire blocking”. |
M-0301-19A | 5/10/19 | APPROVED | 5/13/19 | 119 Mimosa Cir | Ridgefield | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0300-19 | 5/10/19 | APPROVED | 5/10/19 | 75 Eastern Pt. Road | Groton | 1809.5 | Section 1809.5, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “Except where otherwise protected from frost, foundation walls, piers or other permanent supports for buildings and structures shall extend below the established frost line (42 inches)”. |
M-0299-19 | 5/9/19 | APPROVED | 5/10/19 | 118 Plainville Avenue | Unionville | 1030.2.1 | Section 1030.2.1, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “The net clear opening dimensions of emergency escape and rescue window shall be obtained by the normal operation of the window from the inside”. |
M-0298-19 | 5/9/19 | APPROVED | 5/10/19 | 90 Post Road East | Westport | R301.2.1 | |
M-0297-19 | 5/9/19 | APPROVED | 5/10/19 | 524 Worthington Ridge | Berlin | 1009.7 | Section 1009.7, of the 2012 International Building portion of the 2016 State Building Code which states in part that, “Stairways shall have a maximum riser height of 7 inches”. |
M-0296-19 | 5/9/19 | APPROVED | 5/10/19 | 28 High Street | Hartford | 3006.1 | Section 3006.1, of the 2015 International Building Code portion of the 2018 State Building Code. |
M-0295-19B | 5/9/19 | APPROVED | 5/10/19 | 145 Filbert Street | Hamden | R311.7.2(2) | Section R311.7.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0295-19A | 5/9/19 | APPROVED | 5/10/19 | 145 Filbert Street | Hamden | R305.1 | Section R305.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Habitable rooms and hallways shall have a ceiling height of not less than 7 feet”. |
M-0294-19 | 5/8/19 | APPROVED | 5/9/19 | 59 Ethan Allen Highway | Ridgefield | 410.8.10 | |
M-0293-19 | 5/8/19 | DENIED | 5/9/19 | 350 Buckland Road | South Windsor | 1022.5 | Section 1022.5, of the 2012 International Building Code portion of the 2018 State Building Code, which states that “Penetrations into and openings through interior exit stairways are prohibited except for required exit doors, equipment and ductwork necessary for independent ventilation or pressurization, sprinkler piping, standpipes, electrical raceway for the fire department communication and security systems and electrical raceway serving the interior exit stairway and ramp and terminating at a steel box not exceeding 16 square inches”. |
M-0292-19 | 5/8/19 | APPROVED | 5/9/19 | 137 Thames Street | Groton | R101.2 | |
M-0291-19 | 5/7/19 | APPROVED | 5/9/19 | 262A Pearl Street | Enfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0290-19 | 5/7/19 | APPROVED | 5/9/19 | 15 Mountain Road | Wilton | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0289-19 | 5/6/19 | APPROVED | 5/8/19 | 5 Stonybrook Road | Norwalk | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0288-19 | 5/6/19 | APPROVED | 5/8/19 | 1 Park Lane | Brookfield | R326.6.3 | |
M-0287-19 | 5/6/19 | APPROVED | 5/8/19 | 132 Grove Street | Windsor | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0286-19B | 5/6/19 | APPROVED | 5/8/19 | 75 Eastern Point Road | Groton | 1612.4 | Section 1612.4, of the 2012 International Building Code portion of the 2016 State Building Code which sets forth requirements for the “Design and Construction of Buildings and Structures located in flood hazard areas”. |
M-0286-19A | 5/6/19 | APPROVED | 5/8/19 | 75 Eastern Point Road | Groton | 910.3 | Section 910.3, of the 2012 International Building Code portion of the 2016 State Building Code which states in part that, “Smoke and heat vents and draft curtain shall be as specified in Table 910.3 (Draft Curtain Depth 29 Feet)”. |
M-0285-19 | 5/1/19 | APPROVED | 5/3/19 | 657-697 Main Street | Branford | 1009.7.2 | Section 1009.7.2, of the 2012 International Building portion of the 2016 State Building Code which states in part that, “Stairs shall have a maximum riser height of 7 inches and a minimum tread depth shall be 11 inches”. |
M-0284-19 | 5/1/19 | APPROVED | 5/2/19 | 75 Eastern Point Road | Groton | 1012.6 | Section 1012.6, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “All locations where handrails are not continuous between stairway flights, including the top and bottom of a stairway, the handrails shall extend horizontally at least 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser”. |
M-0283-19 | 5/1/19 | APPROVED | 5/2/19 | 35 Leroy Avenue | Darien | 2016SBC | Continued use of the 2016 State Building Code |
M-0282-19B | 5/1/19 | APPROVED | 5/2/19 | 506 Main Street S | Woodbury | 1011.5.2 | Section 1011.5.2, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “The maximum riser height with stairways shall be 7 inches.” |
M-0282-19A | 5/1/19 | APPROVED | 5/2/19 | 506 Main Street S | Woodbury | 1011.5.2 | Section 1011.5.2, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “The maximum riser height with stairways shall be 7 inches.” |
M-0281-19 | 4/29/19 | APPROVED | 5/1/19 | 4 Glenway | New Fairfield | 403.1 | Section 403.1, of the 2012 International Plumbing Code portion of the 2016 State Building Code, which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 403.1”(drink fountain required). |
M-0280-19 | 4/29/19 | APPROVED | 5/1/19 | 211 Main Street | Wethersfield | 507.1.2 | |
M-0279-19B | 5/10/19 | APPROVED | 5/13/19 | 330 Main Street | Wethersfield | 3901.4.1 | |
M-0279-19 | 4/29/19 | APPROVED | 5/1/19 | 330 Main Street | Wethersfield | 3901.4.1 | Section 3901.4.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “A receptacle outlet shall be installed at each wall counter space so that no point along the wall line is more than 24 inches from a receptacle outlet”. |
M-0278-19 | 4/29/19 | APPROVED | 5/1/19 | 20 East Main Street | Avon | 2902.1 | Section 2902.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 2902.1 (Drinking Fountain and Sink Required)” |
M-0277-19 | 4/29/19 | APPROVED | 5/1/19 | 20 Little Fawn Road | Southington | 110.26(A) | Section 110.26(A), of the 2017 National Electrical Code portion of the 2018 State Building Code, which states in part that “Working space for equipment likely to require examination, servicing or maintenance while energized shall comply with the dimensions of 110.26(A)(1), (A2), (A3) and (A4)”. |
M-0276-19 | 4/29/19 | DENIED | 5/1/19 | 45 Hillfield Road | Hamden | 2902.1.2 | Section 2902.1.2, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “The plumbing fixtures located in single-user toilet facilities and bathing rooms, including family or assisted-use toilet and bathing rooms that are required by Section 1109.2.1 of the International Building Code, shall contribute towards the total number of required plumbing fixtures for a building or tenant space”. |
M-0275-19B | 4/26/19 | APPROVED | 4/30/19 | 55 Gilbert Street | West Haven | 705.8.1 | |
M-0275-19A | 4/26/19 | DENIED | 4/30/19 | 55 Gilbert Street | West Haven | 602.1 | Table 602.1, of the 2015 International Building Code portion of the 2018 State Building Code, which states that “Exterior walls shall have a fire-resistance rating not less than specified in Table 602 (1-hour required)”. |
M-0274-19 | 4/26/19 | APPROVED | 4/30/19 | 25 Canal Bank Road | Windsor Locks | 602.4.6.1 | |
M-0273-19 | 4/26/19 | APPROVED | 4/30/19 | 1095 West Street | Southington | 403.2 | Section 403.2, of the 2015 International Plumbing Code portion of the 2018 State Building Code, which states in part that “Where plumbing fixtures are required, separate facilities shall be provided for each sex”. |
M-0272-19 | 4/26/19 | APPROVED | 4/30/19 | 110 Myrtle Avenue | Westport | 1609.3 | Section 1609.3, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “The ultimate design wind speed for the determination of the wind loads shall be determined by Appendix N”. |
M-0271-19 | 4/26/19 | APPROVED | 4/30/19 | 11 Webber Road | Rocky Hill | R311.7.5.2.1 | |
M-0270-19 | 4/26/19 | APPROVED | 4/30/19 | 15 Bluefield Drive | East Hartford | R403.1.4.1(4) | |
M-0269-19 | 4/26/19 | APPROVED | 4/30/19 | 7 Bombard Court | Terryville | 230.2 | Section 230.2, of the 2017 National Electrical Code portion of the 2018 State Building Code, which states in part that “A building shall be supplied by only one service unless permitted in (A) through (D)”. |
M-0268-19 | 4/26/19 | APPROVED | 4/30/19 | 35 Saint James Avenue | Enfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0267-19 | 4/26/19 | APPROVED | 4/30/19 | 32 Hatheway Drive | West Hartford | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0266-19 | 4/26/19 | DENIED | 4/30/19 | 7 Pelham Road | West Hartford | R305.1.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0265-19 | 4/25/19 | APPROVED | 4/30/19 | 41 Laurel Crest Road | Madison | ACE/SE1 7-16 | |
M-0264-19 | 4/24/19 | APPROVED | 4/26/19 | 38 Kayview Avenue | Bethel | R311.7.2 | Section R311.7.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0263-19 | 4/24/19 | APPROVED | 4/26/19 | 6A Edgewater | Branford | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0262-19C | 4/24/19 | APPROVED | 4/25/19 | 300 Prospect Street | New Haven | 1011.11; 1014.2; 1014.6; 1015.2 | Sections 1011.11; 1014.2; 1014.6 and 1015.2 of the 2015 International Building Code portion of the 2018 State Building Code, which sets forth requirements for “handrails and guardrails along stairways”. |
M-0262-19B | 4/24/19 | APPROVED | 4/25/19 | 300 Prospect Street | New Haven | 1023.2 | Section 1023.2 of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “Enclosures for interior exit stairways shall be constructed as 1-hour fire barriers”. |
M-0262-19A | 4/24/19 | APPROVED | 4/25/19 | 300 Prospect Street | New Haven | 712.1.9 | |
M-0261-19 | 4/22/19 | APPROVED | 4/25/19 | 434-124 West Middle Turnpike | Manchester | 240.24(D) | Section 240.24(D), of the 2017 National Electrical Code portion of the 2018 State Building Code, which states in part that “Overcurrent devices shall not be located in clothes closets”. |
M-0260-19 | 4/22/19 | APPROVED | 4/24/19 | 1579 Straits Turnpike | Middlebury | 1006.2.1 | Section 1006.2.1 of the 2015 International Building Code portion of the 2018 State Building Code, states in part that “Two exits or exit access doorways from any space shall be provided with the common path of egress travel distance exceeds the values listed in Table 1006.2.1 (fully sprinklered business use 100 feet)”. |
M-0259-19 | 4/22/19 | APPROVED | 4/24/19 | 551 Courtland Avenue | Bridgeport | R305.1 | Section R305.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Habitable rooms and hallways shall have a ceiling height of not less than 7 feet”. |
M-0258-19 | 4/22/19 | APPROVED | 4/24/19 | 1504 Fairfield Beach Road | Fairfield | ||
M-0257-19 | 4/22/19 | APPROVED | 4/24/19 | 253 Old Kings Highway South | Darien | M1503.4 | Section M1503.4 of the 2012 International Residential Code portion of the 2016 State Building Code which states in part, “Exhaust hood systems capable of exhausting in excess of 400 cubic feet per minute (0.19 m3/s) shall be provided with makeup air at a rate approximately equal to the exhaust air rate.” |
M-0256-19 | 4/22/19 | APPROVED | 4/25/19 | 50 River Road | Cos Cob | 102.1.2 | Section 102.1.2 of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Two exits shall be provided from every story”. |
M-0255-19 | 4/22/19 | APPROVED | 4/23/19 | 1339 Tolland Turnpike | Manchester | ||
M-0254-19 | 4/18/19 | APPROVED | 4/23/19 | 189 Jerry Browne Road | Mystic | ||
M-0253-19 | 4/17/19 | APPROVED | 4/23/19 | 8 Farm Road | New Canaan | ||
M-0252-19 | 4/17/19 | APPROVED | 4/23/19 | 87 Arrowhead Road | Windsor | ||
M-0251-19 | 4/16/19 | APPROVED | 4/18/19 | 25 Hebron Street | Middletown | R311.7.6(2) | |
M-0250-19 | 4/16/19 | WITHDREW | 4/17/19 | 159 Colonial Road | Stamford | WITHDREW REQUEST | |
M-0249-19 | 4/16/19 | APPROVED | 4/16/19 | 41 Sunset Trail | New Fairfield | R802.5 | |
M-0248-19 | 4/16/19 | APPROVED | 4/16/19 | 1515-1517 Main Street | East Hartford | 1504.5 | Section 1504.5, of the 2012 International Building Code portion of the 2016 State Building Code, which sets forth requirements for the “Edge securement for low-slope roofs”. |
M-0247-19 | 4/12/19 | DENIED | 4/16/19 | 40 Commerce Drive | Cromwell | 1020.1 | Section 1020.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “The corridors within a business use serving an occupied load of more than 30 shall be rated for 1 hour”. |
M-0246-19 | 4/12/19 | APPROVED | 4/16/19 | 1 Pembroke Street a/k/a 10 Middle Street |
Bridgeport | 304.11 | Section 304.11, of the 2015 International Mechanical Code portion of the 2018 State Building Code |
M-0245-19 | 4/12/19 | APPROVED | 4/16/19 | 100 Oakview Drive | Trumbull | Section 309.4 of the 2009 A117.1 | |
M-0244-19 | 4/12/19 | DENIED | 4/16/19 | 20 Randall Circle | Windsor | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0243-19 | 4/12/19 | APPROVED | 4/16/19 | 14 Jansen Lane | North Haven | 201-52(C)(2) | Section 210-52(C)(2), of the 2017 National Electrical Code portion of the 2018 State Building Code, which states in part that |
M-0242-19 | 4/12/19 | APPROVED | 4/16/19 | 40 Oak Ridge Drive | Hamden | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0241-19 | 4/12/19 | APPROVED | 4/16/19 | 1033 Manchester Road | Glastonbury | 602.10 | Section 602.10, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for wall bracing. |
M-0240-19B | 4/12/19 | APPROVED | 4/16/19 | 1799 Summer Street | Stamford | 1009.5 | Section 1009.5, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “The minimum, headroom in all parts of the stairway shall not be less than 6 feet, 8 inches measured vertically from the sloped plane adjoining the tread nosing or from the floor surface of the landing or platform”. |
M-0240-19A | 4/12/19 | APPROVED | 4/16/19 | 1799 Summer Street | Stamford | 1007.7.4 | Section 1007.7.4, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “Exterior walls separating the exterior area of assisted rescue from the interior of the building shall have a minimum fire-resistance rating of 1 hour, rated for exposure to fire from the inside. Openings within such fire-resistance-rated exterior walls shall be protected”. |
M-0239-19 | 4/11/19 | APPROVED | 4/16/19 | 23 Brush Island Road | Darien | E3901.4.1 | |
M-0238-19B | 4/11/19 | APPROVED | 4/16/19 | 17 Marshall Drive | Enfield | R311.7.2 | Section R311.7.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0238-19A | 4/11/19 | APPROVED | 4/16/19 | 17 Marshall Drive | Enfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0237-19 | 4/11/19 | APPROVED | 4/16/19 | 21 Richmond Drive | Darien | E3901.4.1 | |
M-0236-19 | 4/11/19 | APPROVED | 4/16/19 | 165 Old Farms Road | Torrington | R305.1(2) | The ceiling height above bathroom and toilet room fixtures shall be such that the fixture is capable of being used for its intended purpose. A shower or tub equipped with a shower head shall have a ceiling height of not less than 6 feet 8 inches (2032 mm) above an area of not less than 30 inches (762 mm) by 30 inches (762 mm) at the showerhead. |
M-0235-19 | 4/11/19 | APPROVED | 4/16/19 | 394 Deercliff Road | Avon | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0234-19 | 4/10/19 | APPROVED | 4/16/19 | 60 Blossom Way | Southington | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0233-19 | 4/10/19 | APPROVED | 4/16/19 | 65 Bailey's Road | Wethersfield | R305.1(2) | The ceiling height above bathroom and toilet room fixtures shall be such that the fixture is capable of being used for its intended purpose. A shower or tub equipped with a shower head shall have a ceiling height of not less than 6 feet 8 inches (2032 mm) above an area of not less than 30 inches (762 mm) by 30 inches (762 mm) at the showerhead. |
M-0232-19 | 4/10/19 | DENIED | 4/16/19 | 105 Toddy Hill Road | Sandy Hook | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0231-19 | 4/8/19 | APPROVED | 4/15/19 | 1124 Hartford Turnpike | North Haven | R303.1 | Section R303.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Habitable rooms shall have windows with an openable area to the outdoors of not less than 4 percent of the floor area being ventilated”. |
M-0230-19 | 4/8/19 | APPROVED | 4/15/19 | 518 Clintonville Road | North Haven | 807.1 | Section 807.1, of the 2015 International Residential Code portion of the 2018State Building, which states in part that “In buildings with combustible ceiling or roof construction, an attic access opening shall be provided to attic areas that exceed 30 square feet and have a vertical height of 30 inches”. |
M-0229-19 | 4/8/19 | APPROVED | 4/15/19 | 75 Eastern Pt. Road | Groton | 1809.5 | Section 2902.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 2902.1.” |
M-0228-19 | 4/8/19 | DENIED | 4/15/19 | 99 Taconic Road | Greenwich | AG105.2 | |
M-0227-19 | 4/8/19 | APPROVED | 4/15/19 | 256 Umpawaug Road | Redding | P2903.9.3 | |
M-0226-19 | 4/8/19 | APPROVED | 4/15/19 | 33 Jobs Hill Road | Ellington | 312.1 | Section 312.1, of the 2003 International Building portion of the 2005 State Building Code which states in part that, “Livestock Shelters and Agriculture Buildings are classified as Group U Structure”. |
M-0225-19 | 4/8/19 | No Mod Req. | 4/15/19 | 351 Kettletown Road | Southbury | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0224-19 | 4/8/19 | APPROVED | 4/15/19 | 100 Arch Street | Greenwich | 1609.3 | Section 1609.3, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “The basic wind speed in miles per hour for the determination of wind loads on buildings and structures shall be determined by Appendix N”. |
M-0223-19 | 4/8/19 | APPROVED | 4/15/19 | 63 Saddle Ridge Road | Wilton | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0222-19 | 4/8/19 | APPROVED | 4/15/19 | 360 Broad Street | Hartford | 304.11 | Section 304.11, of the 2015 International Mechanical Code portion of the 2018 State Building Code |
M-0221-19 | 4/8/19 | APPROVED | 4/15/19 | 484 Valley Road | Greenwich | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0220-19 | 4/8/19 | APPROVED | 4/15/19 | 75 Griffin Street | Stratford | 1009.7.2 | Section 1009.7.2, of the 2012 International Building portion of the 2016 State Building Code which states in part that, “Stairs shall have a maximum riser height of 7 inches and a minimum tread depth shall be 11 inches”. |
M-0219-19 | 4/5/19 | WITHDREW | 131 Blue Bird Drive | Naugatuck | WITHDREW REQUEST | ||
M-0218-19 | 4/5/19 | APPROVED | 4/10/19 | 479 Hazard Avenue | Enfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0217-19 | 4/5/19 | APPROVED | 4/10/19 | 228 Abbe Road | Enfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0216-19 | 4/4/19 | APPROVED | 4/10/19 | 252 Mountain Road | Wilton | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0215-19 | 4/4/19 | APPROVED | 4/10/19 | 12 Tunxis Road | Madison | ACE/SE1 7-16 | |
M-0214-19 | 4/4/19 | APPROVED | 4/10/19 | 97 Newberry Road | East Windsor | C503.3.1 | |
M-0213-19C | 4/4/19 | DENIED | 4/10/19 | 36 Brookfield Drive | East Hartford | R609.1 | |
M-0213-19B | 4/4/19 | APPROVED | 4/10/19 | 36 Brookfield Drive | East Hartford | R905.2 | |
M-0213-19A | 4/4/19 | DENIED | 4/10/19 | 36 Brookfield Drive | East Hartford | R109.4 | |
M-0212-19C | 4/3/19 | APPROVED | 4/10/19 | 383 Bennetts Farm Road | Ridgefield | R302.11 | Section R302.11, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for “fire blocking”. |
M-0212-19B | 4/3/19 | APPROVED | 4/10/19 | 383 Bennetts Farm Road | Ridgefield | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the “building thermal envelope” |
M-0212-19A | 4/3/19 | APPROVED | 4/10/19 | 383 Bennetts Farm Road | Ridgefield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0211-19 | 4/3/19 | APPROVED | 4/10/19 | 497 Danbury Road | Ridgefield | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the “building thermal envelope” |
M-0210-19 | 4/3/19 | APPROVED | 4/10/19 | 1077 Boston Post Road | Darien | 2902.1 | Section 2902.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 2902.1.” |
M-0209-19B | 4/3/19 | APPROVED | 4/10/19 | 41 Jackson Street | West Hartford | R311.7.2 | Section R311.7.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0209-19A | 4/3/19 | APPROVED | 4/10/19 | 41 Jackson Street | West Hartford | R311.7.1 | Section R311.7.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The width of existing stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall not be less than 32 inches in clear width at all points above the permitted handrail height and below the required headroom height. |
M-0208-19 | 4/2/19 | APPROVED | 4/10/19 | 445 Eastern Point Road | Groton | 1017.2 | Section 1017.2, of the 2015 International Building Code portion of the 2018 State Building Code, which limits the travel distance to an exit within an H-3 occupancy to 150 feet. |
M-0207-19 | 4/2/19 | APPROVED | 4/10/19 | 898 Silas Dean Highway | Wethersfield | 2902.1 | Section 2902.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 2902.1.” |
M-0206-19B | 4/1/19 | APPROVED | 4/10/19 | 21 Broadway | New Haven | 2902.2 | Section 2902.2, of the 2012 International Building Code portion of the 2016 State Building Code which states in part that “Where plumbing fixtures are required, separate facilities shall be provided for each sex”. |
M-0206-19A | 4/1/19 | APPROVED | 4/10/19 | 21 Broadway | New Haven | 1010.1.2.1 | Section 1010.1.2.1 of the 2015 International Building Code portion, of the 2018 State Building Code which states in part that “Doors shall swing in the direction of egress travel within an exit enclosure”. |
M-0205-19B | 4/1/19 | APPROVED | 4/10/19 | 531 Middletown Avenue | New Haven | 403.3.3 | Section 403.3.3 of the 2015 International Plumbing Code portion, of the 2018 State Building Code which states in part that “The required toilet facilities shall be located not more than one story above the space required to be provided within toilet facilities”. |
M-0205-19A | 4/1/19 | APPROVED | 4/10/19 | 531 Middletown Avenue | New Haven | 1004.1.2 | Section 1004.1.2 of the 2015 International Building Code portion, of the 2018 State Building Code which states in part that “The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.2”. |
M-0204-19 | 4/1/19 | APPROVED | 4/3/19 | 38 Bantam Lake Road | Bantam | 403.2 | Section 403.2, of the 2015 International Plumbing Code portion of the 2018 State Building Code, which states in part that “Where plumbing fixtures are required, separate facilities shall be provided for each sex”. |
M-0203-19 | 4/1/19 | APPROVED | 4/3/19 | 129 Griffin Road North | Bloomfield | 706.2 | Section 706.2, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Fire walls shall be designed and constructed to allow collapse of construction on either side without collapse of the wall under fire conditions.” |
M-0202-19 | 4/1/19 | APPROVED | 4/3/19 | 960-954 Main Street | Branford | 1020.3 | Section 1020.3, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “The minimum width of corridors shall be unobstructed”. |
M-0201-19 | 3/29/19 | APPROVED | 4/3/19 | 36 Bailey Road | Avon | R310.1 | |
M-0200-19 | 3/29/19 | DENIED | 4/3/19 | 944 Hopmeadow Street | Simsbury | 1006.3 | Section 1006.3.2, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “The emergency means of egress illumination system shall be arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to the opening of a circuit breaker or fuse”. |
M-0199-19 | 3/29/19 | APPROVED | 4/3/19 | 35 Old Park Lane Road | New Milford | 903.2.8 | Section 903.2.8, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings within a Group R fire area”. |
M-0198-19 | 3/29/19 | APPROVED | 4/3/19 | 263 Treaser Boulevard | Stamford | 7.2.1.6.3 | |
M-0197-19 | 3/29/19 | APPROVED | 4/3/19 | 18 Bailey Road | Avon | R310.1 | |
M-0196-19 | 3/29/19 | APPROVED | 4/3/19 | 78 Conwell Road | Meriden | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0195-19 | 3/29/19 | APPROVED | 4/3/19 | 36 Vina Lane | Brooklyn | 2016SBC | Continued use of the 2016 State Building Code |
M-0194-19 | 3/29/19 | APPROVED | 4/3/19 | 42-62 Water Street | Southington | 2016SBC | Continued use of the 2016 State Building Code |
M-0193-19 | 3/28/19 | APPROVED | 3/29/19 | 89 Cipolla Drive | East Hartford | R403.1.4.1 | Section R403.1.4.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Except where otherwise protected from frost, foundation walls, piers or other permanent supports for buildings and structures shall extend below the established frost line (42 inches)”. |
M-0192-19 | 3/28/19 | APPROVED | 3/29/19 | 155 Forest Street | East Hartford | R403.1.4.1 | Section R403.1.4.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Except where otherwise protected from frost, foundation walls, piers or other permanent supports for buildings and structures shall extend below the established frost line (42 inches)”. |
M-0191-19 | 3/28/19 | APPROVED | 3/29/19 | 614 Shippan Avenue | Stamford | 406.3.2 | |
M-0190-19 | 3/28/19 | DENIED | 3/29/19 | 149 Natchaug Drive | Glastonbury | R311.7.2 | Section R311.7.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0189-19 | 3/28/19 | APPROVED | 3/29/19 | 1401 Kings Highway | Fairfield | 705.5 | Section 705.5, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “The required fire-resistance rating of exterior walls with a fire separation distance of less than or equal to 10 feet (3048 mm) shall be rated for exposure to fire from both sides”. |
M-0188-19 | 3/28/19 | APPROVED | 3/29/19 | 11 Shoham Road | East Windsor | 334.12(A)(2) | “NM cables shall not be permitted to be exposed within a dropped or suspended ceiling cavity in other than one and two-family and multifamily dwellings”. |
M-0187-19 | 3/28/19 | APPROVED | 3/29/19 | 95 South Main Street | East Granby | C503.3.1 | |
M-0186-19 | 3/26/19 | APPROVED | 3/28/19 | 1020 West Street | Southington | 2016SBC | Continued use of the 2016 State Building Code |
M-0185-19 | 3/25/19 | APPROVED | 3/28/19 | 189 Fort Hill Road | Groton | 706.1 | Section 706.1, of the 2012 International Building Code portion of the 2016 State Building Code which sets forth requirements for the construction of fire walls. |
M-0184-19 | 3/25/19 | DENIED | 3/28/19 | 87 Franklin Street | Stamford | 503.1 | Section 503.1, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “The building height and area shall not exceed the limits specified in Table 503 based on the type of construction as determined by Section 602 and the occupancies as determined by Section 302 except as modified hereafter”. |
M-0183-19 | 3/25/19 | APPROVED | 3/28/19 | 3 E. Lake Road | New Fairfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0182-19 | 3/25/19 | APPROVED | 3/28/19 | 11 Trifiro Circle | Glastonbury | 310.2.1 | Section 310.2.1, of the 2015 CABO One and Two Family Dwelling Code portion of the 2018 State Building Code, which states in part that “All egress or rescue windows from sleeping rooms must have a net clear opening of 5.7 square feet. The minimum net clear opening height shall be 24 inches. The minimum net clear opening width shall be 20 inches”. |
M-0181-19 | 3/25/19 | DENIED | 3/28/19 | 252 Mountain Road | Wilton | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0180-19 | 3/22/19 | APPROVED | 3/28/19 | 87 Lake Drive | New Milford | R405.1 | |
M-0179-19 | 3/22/19 | APPROVED | 3/28/19 | 36 Main Street South | Bethlehem | 604.5.1 | |
M-0178-19 | 3/22/19 | APPROVED | 4/9/19 | 2 East Main Street | Bridgeport | 2019 Edition of NFPA 14 | It is my decision to approve this modification, as requested, to utilize the approved language of NFPA 14, in lieu of the requirements of the 2018 State Building Code. This decision is based on the approved language of the 2019 Standard which recognizes the use of high density polyethylene pipe for standpipe systems at marines and boatyards. |
M-0177-19 | 3/22/19 | APPROVED | 3/22/19 | 144 Edgewood Drive | South Windsor | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0176-19 | 3/21/19 | APPROVED | 3/22/19 | 388 Danbury Road | New Milford | C503.3.1 | |
M-0175-19 | 3/21/19 | APPROVED | 3/22/19 | 915 North Main Street | Waterbury | 1009.9.2 | Section 1009.9.2, of the 2012 International Building Code portion of the 2016 State Building Code which states in part that “Exterior stairways in climates subject to snow and ice shall be protected to prevent the accumulation of same”. |
M-0174-19 | 3/20/19 | APPROVED | 3/22/19 | 10 East Main Street | Bridgeport | C402.5.7 | |
M-0173-19B | 3/20/19 | APPROVED | 3/22/19 | 50 Line Street | Glastonbury | 1604.8 / 1809.5 | Sections 1604.8 (Anchorage) and 1809.5 (Frost Protection), of the 2015 International Building Code portion of the 2018 State Building Code. |
M-0173-19A | 3/20/19 | APPROVED | 3/22/19 | 50 Line Street | Glastonbury | 411.4 | Section 411.1, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “Special Amusement Buildings shall be equipped with automatic sprinkler systems”. |
M-0172-19 | 3/20/19 | APPROVED | 3/22/19 | 90 Naugatuck Avenue | Milford | 1022.4 | Section 1022.4, of the 2012 International Building Code portion of the 2018 State Building Code, which states that “Openings into interior exit stairways shall be limited to those necessary for exit access to the enclosure from normally occupied spaces and for egress from the enclosure”. |
M-0171-19 | 3/19/19 | APPROVED | 3/22/19 | 15 Brittany Circle | Cromwell | 110.26 | Section 110.26, of the 2017 National Electrical Code portion of the 2018 State Building Code, which states in part that “Access and working space shall be provided and maintained about all electrical equipment to permit ready and safe operation of maintenance of such equipment”. |
M-0170-19B | 3/19/19 | APPROVED | 3/20/19 | 208 Amherst Street | New Britain | R305.1(3) | Section R305.1(3), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The height under beams, girders, ducts or other obstructions in basements containing habitable space shall be of 6 feet, 4 inches”. |
M-0170-19A | 3/19/19 | APPROVED | 3/20/19 | 208 Amherst Street | New Britain | R305.1(2) | The ceiling height above bathroom and toilet room fixtures shall be such that the fixture is capable of being used for its intended purpose. A shower or tub equipped with a shower head shall have a ceiling height of not less than 6 feet 8 inches (2032 mm) above an area of not less than 30 inches (762 mm) by 30 inches (762 mm) at the showerhead. |
M-0169-19 | 3/19/19 | APPROVED | 3/20/19 | 35 Belle Avenue | Enfield | R403.1.4.1 | Section R403.1.4.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Except where otherwise protected from frost, foundation walls, piers or other permanent supports for buildings and structures shall extend below the established frost line (42 inches)”. |
M-0168-19 | 3/18/19 | APPROVED | 3/20/19 | 184 Point Beach Drive | Milford | R325.6 | |
M-0167-19 | 3/18/19 | APPROVED | 3/20/19 | 10 Jim Gallagher Way, Unit 9 | Simsbury | 1014.6 | Section 1014.6, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “At locations where handrails are not continuous between stairway flights, including the top and bottom of a stairway, the handrails shall extend horizontally at least 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser”. |
M-0166-19 | 3/18/19 | APPROVED | 3/20/19 | 88 Gardiner Street | Darien | R305.1(2) | The ceiling height above bathroom and toilet room fixtures shall be such that the fixture is capable of being used for its intended purpose. A shower or tub equipped with a shower head shall have a ceiling height of not less than 6 feet 8 inches (2032 mm) above an area of not less than 30 inches (762 mm) by 30 inches (762 mm) at the showerhead. |
M-0165-19 | 3/18/19 | APPROVED | 3/20/19 | 210 Plumb Road | Middletown | 110.26(A)(1) | Section 110.26(A)(1), of the 2017 National Electrical Code portion of the 2018 State Building Code, which states in part that “Working space for equipment likely to require examination, servicing or maintenance while energized shall not be less than indicated in Table 110.26(A)(1) (3 feet)”. |
M-0164-19 | 3/18/19 | APPROVED | 3/20/19 | 89 Daventry Hill | Avon | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the “building thermal envelope” |
M-0163-19 | 3/18/19 | APPROVED | 3/20/19 | 135 Oldfield Road | Fairfield | R305.1 | Section R305.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Habitable rooms and hallways shall have a ceiling height of not less than 7 feet”. |
M-0162-19 | 3/15/19 | APPROVED | 3/19/19 | 8 Independence Cir | Southbury | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0161-19 | 3/15/19 | APPROVED | 3/19/19 | 18 Nashville Road | Bethel | 903.2.8 | Section 903.2.8, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings within a Group R fire area”. |
M-0160-19 | 3/14/19 | APPROVED | 3/19/19 | 98 Garden Street | Hartford | 110.26(A)(1) | Section 110.26(A)(1), of the 2017 National Electrical Code portion of the 2018 State Building Code, which states in part that “Working space for equipment likely to require examination, servicing or maintenance while energized shall not be less than indicated in Table 110.26(A)(1) (3 feet)”. |
M-0159-19 | 3/14/19 | APPROVED | 3/18/19 | 445 Whitney Road Extension | Storrs | 410.62(C)(1) | |
M-0158-19 | 3/13/19 | APPROVED | 3/18/19 | 633 Oak Street | East Hartford | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0157-19 | 3/12/19 | APPROVED | 3/18/19 | 17 Dartmouth Lane | Danbury | R305.1(2) | The ceiling height above bathroom and toilet room fixtures shall be such that the fixture is capable of being used for its intended purpose. A shower or tub equipped with a shower head shall have a ceiling height of not less than 6 feet 8 inches (2032 mm) above an area of not less than 30 inches (762 mm) by 30 inches (762 mm) at the showerhead. |
M-0156-19 | 3/12/19 | APPROVED | 3/18/19 | 3 Powder Ridge Road | Enfield | 2902.1 | Section 2902.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 2902.1.” |
M-0155-19 | 3/12/19 | APPROVED | 3/18/19 | 35 Oak Street | Manchester | 1004.1.2 | Section 1004.1.2 of the 2015 International Building Code portion, of the 2018 State Building Code which states in part that “The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.2”. |
M-0154-19 | 3/11/19 | APPROVED | 3/18/19 | 24 Arrowhead Road | Brookfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0153-19 | 3/11/19 | APPROVED | 3/18/19 | 38 Sycamore Street | Windsor | R311.6.3.1 / R312.1 | |
M-0152-19 | 3/8/19 | APPROVED | 3/12/19 | 72 Franklin Street | Stamford | 705.5 | Section 705.5, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “The required fire-resistance rating of exterior walls with a fire separation distance of less than or equal to 10 feet (3048 mm) shall be rated for exposure to fire from both sides”. |
M-0151-19 | 3/8/19 | APPROVED | 3/12/19 | 143 Empress Drive | Southington | R311.7.6 | Section R311.7.6, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The depth in the direction of travel of landing of existing stairs serving existing basement be converted to habitable space shall not be less than 32 inches”. |
M-0150-19 | 3/8/19 | APPROVED | 3/12/19 | 102 Westminster Drive | West Hartford | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0149-19 | 3/8/19 | APPROVED | 3/12/19 | 50-52 Main Street | Torrington | 705.8.1 | |
M-0148-19B | 3/8/19 | APPROVED | 3/12/19 | 22 Main Street | East Lyme | 1015.3 | Section 903.2.11.1, of the 2012 International Building Code portion of the 2016 State Building Code which sets forth requirements for stories and basements without openings. |
M-0148-19A | 3/8/19 | APPROVED | 3/12/19 | 22 Main Street | East Lyme | 1014.6 | Section 1014.6, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “At locations where handrails are not continuous between stairway flights, including the top and bottom of a stairway, the handrails shall extend horizontally at least 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser”. |
M-0147-19B | 3/8/19 | APPROVED | 3/12/19 | 252 Bogue Road | Harwinton | 903.2.11.1 | |
M-0147-19A | 3/8/19 | APPROVED | 3/12/19 | 252 Bogue Road | Harwinton | 1015.1 | Section 1015.1, of the 2012 International Building Code portion of the 2016 State Building Code which sets forth requirements for determining the amount of exits that are required. |
M-0146-19 | 3/8/19 | APPROVED | 3/12/19 | 7 New York Road | Oakdale | R311.7.5.1 | Section R311.7.5.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 of an inch”. |
M-0145-19 | 3/6/19 | DENIED | 3/7/19 | 70 Sunrise Drive | Avon | N1103.3.3 | |
M-0144-19 | 3/6/19 | APPROVED | 3/7/19 | 345 Mountain Road | Wilton | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0143-19 | 3/6/19 | APPROVED | 3/7/19 | 40 Mohawk Lane | Wethersfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0142-19 | 3/5/19 | APPROVED | 3/7/19 | 239 Ridgewood Road | West Hartford | 110.26(A)(1) | Section 110.26(A)(1), of the 2017 National Electrical Code portion of the 2018 State Building Code, which states in part that “Working space for equipment likely to require examination, servicing or maintenance while energized shall not be less than indicated in Table 110.26(A)(1) (3 feet)”. |
M-0141-19 | 3/4/19 | APPROVED | 3/7/19 | 1832 Dixwell Avenue | Hamden | 2902.2 | Section 2902.2, of the 2012 International Building Code portion of the 2016 State Building Code which states in part that “Where plumbing fixtures are required, separate facilities shall be provided for each sex”. |
M-0140-19 | 3/4/19 | APPROVED | 3/5/19 | 39 Lindeman Drive | Trumbull | 2902.1 | Section 2902.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 2902.1.” |
M-0139-19 | 3/4/19 | APPROVED | 3/5/19 | 15 Shields Road | Darien | 210.52(C)(1) | Section 210.52(C)(1), of the 2014 National Electrical Code portion of the 2016 State Building Code which states in part that “A receptacle outlet shall be installed at each wall counter space so that no point along the wall line is more than 24 inches from a receptacle outlet”. |
M-0138-19 | 3/4/19 | APPROVED | 3/5/19 | 87 Union Street | New Haven | 403.1 | Section 403.1, of the 2012 International Plumbing Code portion of the 2016 State Building Code, which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 403.1”(drink fountain required). |
M-0137-19 | 3/4/19 | DENIED | 3/5/19 | 163 Victoria Road | New Britain | R311.7.2 | Section R311.7.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0136-19B | 3/4/19 | APPROVED | 3/5/19 | 189 Fort Hill Road | Groton | 1009.13 | Section 1009.13, of the 2012 International Building Code portion of the 2016 State Building Code which set forth requirements for Alternating tread devices are allowed. |
M-0136-19A | 3/4/19 | APPROVED | 3/5/19 | 189 Fort Hill Road | Groton | 603.1 | Section 603.1, of the 2012 International Building Code portion of the 2016 State Building Code which set forth requirements for where combustible materials are allowed in building construction of non-combustible construction. |
M-0135-19 | 3/1/19 | APPROVED | 3/5/19 | 20 Coen Street | Naugatuck | P2705.1(5) | Section P2705.1(5), of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “there shall be a minimum of 15 inches from the center of a lavatory wall”. |
M-0134-19 | 3/1/19 | DENIED | 3/5/19 | 29 Northbrick Lane | Wethersfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0133-19B | 3/1/19 | APPROVED | 3/5/19 | 102 Parkview Drive | Avon | R302.11 | Section R302.11, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for “fire blocking”. |
M-0133-19A | 3/1/19 | APPROVED | 3/5/19 | 102 Parkview Drive | Avon | R310.2.1 | |
M-0132-19B | 3/1/19 | APPROVED | 3/5/19 | 14 May Avenue | Naugatuck | R310.2.1 | |
M-0132-19A | 3/1/19 | APPROVED | 3/5/19 | 14 May Avenue | Naugatuck | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the “building thermal envelope”. |
M-0131-19 | 2/28/19 | APPROVED | 3/1/19 | 141 Welch Road | Southington | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the “building thermal envelope”. |
M-0130-19B | 2/27/19 | APPROVED | 3/14/19 | 630 State Street | New Haven | 503.1 | Section 503.1, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “The Building height, number of stories and building area shall not exceed the limits specified in Section 504 and 506 based on the construction type”. |
M-0130-19A | 2/27/19 | APPROVED | 3/14/19 | 630 State Street | New Haven | 1011.2 | Section 1011.2, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “The minimum width of stairways shall be 44 inches”. |
M-0129-19 | 2/27/19 | APPROVED | 3/1/19 | 28 Indian Run | Enfield | R311.7.2 | Section R311.7.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0128-19 | 2/27/19 | APPROVED | 3/1/19 | 114 Spring Glen Road | Niantic | E3405.2 | Section E3405.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The working space for electrical equipment shall be clear and shall extend from the floor to a height of 6 feet, 6 inches or the height of the equipment whichever is greater”. |
M-0127-19 | 2/26/19 | APPROVED | 2/27/19 | 7 Brown Street | Darien | M1503.4 | Section M1503.4 of the 2012 International Residential Code portion of the 2016 State Building Code which states in part, “Exhaust hood systems capable of exhausting in excess of 400 cubic feet per minute (0.19 m3/s) shall be provided with makeup air at a rate approximately equal to the exhaust air rate.” |
M-0126-19 | 2/25/19 | APPROVED | 2/27/19 | 7 Meadowbrook Road | New Fairfield | 2016SBC | Continued use of the 2016 State Building Code |
M-0125-19 | 2/25/19 | APPROVED | 2/27/19 | 41 Sawmill Lane | Greenwich | M1503.4 | Section M1503.4 of the 2012 International Residential Code portion of the 2016 State Building Code which states in part, “Exhaust hood systems capable of exhausting in excess of 400 cubic feet per minute (0.19 m3/s) shall be provided with makeup air at a rate approximately equal to the exhaust air rate.” |
M-0124-19 | 2/22/19 | APPROVED | 2/27/19 | 134 Winding Lane | East Hartford | R317.1(5) | Section R317.1 #5, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Wood siding sheathing and wall framing on the exterior wall of a building having a clearance of less than 6 inches to grade shall be wood that is preservative-treated”. |
M-0123-19 | 2/22/19 | DENIED | 2/27/19 | 115 North Water Street | Greenwich | R302.1 | Section R302.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Exterior walls located less than 5 feet from a property line shall be tested for exposure from both sides”. |
M-0122-19 | 2/22/19 | APPROVED | 2/27/19 | 565 Newfield Avenue | Stamford | 2902.2 | Section 2902.2, of the 2012 International Building Code portion of the 2016 State Building Code which states in part that “Where plumbing fixtures are required, separate facilities shall be provided for each sex”. |
M-0121-19 | 2/22/19 | No Mod Req. | 2/27/19 | 49 Weston Road | Westport | 903.2.3 | Section 903.2.3, of the 2015 International Building Code portion of the proposed 2018 State Building Code which states in part that “An automatic sprinkler system shall be provided throughout all Group E Fire areas greater than 12,000 square foot in area”. |
M-0120-19 | 2/22/19 | APPROVED | 2/27/19 | 880 Post Road East | Westport | 2016SBC | Continued use of the 2016 State Building Code |
M-0119-19 | 2/27/19 | APPROVED | 3/1/19 | 234 Enfield Avenue | Fairfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0118-19 | 2/22/19 | APPROVED | 2/27/19 | 512-516 Middletown Road | Darien | 1003.5 | Section 1003.5, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “Where changes in elevation of less than 12 inches exist in the means of egress, sloped surfaces shall be used”. |
M-0117-19 | 2/22/19 | APPROVED | 2/27/19 | 12 Wiquetequock Passage | Stonington | E3405.1 | Section E3405.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The access and working space shall be provided and maintained around all electrical equipment to permit ready and safe operation”. |
M-0116-19 | 2/22/19 | APPROVED | 2/25/19 | 180 Millstone Road | Wilton | R311.7.5.1 and R311.7.5.2 | Section R311.7.5.1 and R311.7.5.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The maximum riser height is 8 ¼ inches and the minimum tread depth is 9 inches for stairways”. |
M-0115-19 | 2/20/19 | APPROVED | 2/21/19 | 189 Fort Hill Road | Groton | 404.2.3.2 | Section 404.2.3.2, of the 2009 ICC A117.1 portion of the 2018 State Building Code. |
M-0114-19 | 2/20/19 | APPROVED | 2/21/19 | 207 Oakwood Avenue | West Hartford | 1014.6 | Section 1014.6, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “At locations where handrails are not continuous between stairway flights, including the top and bottom of a stairway, the handrails shall extend horizontally at least 12 inches beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser”. |
M-0113-19 | 2/20/19 | APPROVED | 2/21/19 | 28 Prospect Street | Enfield | 1011.2 | Section 1011.2, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Stairway serving an occupant load of less than 50 shall have a width of not less than 36 inches”. |
M-0112-19 | 2/20/19 | APPROVED | 2/21/19 | 10 Greenwich Avenue | Greenwich | 2902.2 | Section 2902.2, of the 2012 International Building Code portion of the 2016 State Building Code which states in part that “Where plumbing fixtures are required, separate facilities shall be provided for each sex”. |
M-0111-19 | 2/20/19 | APPROVED | 2/21/19 | 138 Holly Hill Road | Southington | 210.52(C)(2) | Section 210.52(C)(2), of the 2017 National Electrical Code portion of the 2016 State Building Code which states in part that “A receptacle outlet shall be installed at each island counter space with a long dimension of 24 inches or greater and a short dimension of 12 inches or greater". |
M-0110-19 | 2/20/19 | APPROVED | 2/21/19 | 121 Evening Star Drive | Naugatuck | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the “building thermal envelope” |
M-0109-19 | 2/20/19 | APPROVED | 2/21/19 | 39 Miles Standish | West Hartford | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0108-19 | 2/20/19 | APPROVED | 2/21/19 | 12 Fair Lane | New Fairfield | 2016SBC | Continued use of the 2016 State Building Code |
M-0107-19 | 2/19/19 | No Mod Req. | 2/21/19 | 233 Warren Hill Road | Cornwall Bridge | R312.1.1 | Section R312.1.1, of the 2015 International Residential Code portion of the 2018 State Building Code which states in part that “Walking surfaces located more than 30 inches above the floor or grade below shall have guardrails not less than 36 inches in height”. |
M-0106-19 | 2/14/19 | APPROVED | 2/21/19 | 14 Brickwalk Lane, 2nd Floor | Farmington | 903.2.8 | Section 903.2.8, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings within a Group R fire area”. |
M-0105-19B | 2/14/19 | APPROVED | 2/21/19 | 8 Patton Drive | Darien | R311.7.2(2) | Section R311.7.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0105-19A | 2/14/19 | APPROVED | 2/21/19 | 8 Patton Drive | Darien | R304.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0104-19B | 2/14/19 | No Mod Req. | 2/21/19 | 60 Portman Street | Torrington | R305.1 | Section R305.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Habitable rooms and hallways shall have a ceiling height of not less than 7 feet”. |
M-0104-19A | 2/14/19 | No Mod Req. | 2/21/19 | 60 Portman Street | Torrington | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0103-19 | 2/13/19 | APPROVED | 2/15/19 | 639 Main Street | East Hartford | 1405.10.2 | Section 1405.10.2, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “Adhered units shall not exceed 24 inches in any face dimension nor more than 3 square feet in total face area and shall not weigh more than 9 pounds per square foot (PSF)”. |
M-0102-19 | 2/13/19 | APPROVED | 2/15/19 | 5 Crestdale Road | Danbury | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0101-19 | 2/13/19 | APPROVED | 2/15/19 | 23 Bess Road | Enfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0100-19 | 2/13/19 | APPROVED | 2/15/19 | 515 Litchfield Turnpike | Bethany | R305.1 | Section R305.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Habitable rooms and hallways shall have a ceiling height of not less than 7 feet”. |
M-0099-19 | 2/13/19 | DENIED | 2/15/19 | 78 Westfield Street | West Haven | R302.1(2) | Table R302.1(2), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The openings are not allowed in exterior walls which are located less than 3 feet from a property line”. |
M-0098-19D | 2/13/19 | DENIED | 2/15/19 | 133 Algin Drive | Middlebury | R311.7.5.1 | Section R311.7.5.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 of an inch”. |
M-0098-19C | 2/13/19 | APPROVED | 2/15/19 | 133 Algin Drive | Middlebury | R311.7.6 | Section R311.7.6, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The depth in the direction of travel of landing of existing stairs serving existing basement be converted to habitable space shall not be less than 32 inches”. |
M-0098-19B | 2/13/19 | APPROVED | 2/15/19 | 133 Algin Drive | Middlebury | R311.7.2 | Section R311.7.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0098-19A | 2/13/19 | APPROVED | 2/15/19 | 133 Algin Drive | Middlebury | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0097-19 | 2/13/19 | APPROVED | 2/14/19 | 25 Mead Avenue | Greenwich | 604.5.2 | Section 604.5.2, of the 2009 ANSI A117.1-2009 portion of the 2018 State Building Code. |
M-0096-19 | 2/13/19 | APPROVED | 2/14/19 | 61 King Street | East Hartford | R905.2.8.5 | Section R905.2.8.5, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “A drip edge shall be provided at eaves and rake edges of shingle roofs. . ..Drip edges shall be mechanically fastened to the roof deck at not more than 12 inches (305 mm) o.c. with fasteners as specified in Section R905.2.5. Underlayment shall be installed over the drip edge along eaves and under the drip edge along rake edges”. |
M-0095-19 | 2/11/19 | APPROVED | 2/14/19 | 534 Oak Street | East Hartford | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the “building thermal envelope” |
M-0094-19 | 2/8/19 | APPROVED | 2/14/19 | Lumber Store Bldg #610 and Lumber Store Bldg #611 | Groton | 1612.4 | Section 1612.4, of the 2012 International Building Code portion of the 2016 State Building Code which sets forth requirements for the “Design and Construction of Buildings and Structures located in flood hazard areas”. |
M-0093-19 | 1/2/19 | APPROVED | 2/13/19 | 4 Broadway | Norwich | 10101.2.1 | Section 10101.2.1, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that "Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons" |
M-0092-19 | 2/7/19 | WITHDREW | 2/13/19 | WITHDREW REQUEST | WITHDREW REQUEST | WITHDREW REQUEST | |
M-0091-19 | 2/8/19 | A | 2/11/19 | 10 Deer Park Court | Greenwich | R311.7.2 | Section R311.7.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 4 inches”. |
M-0090-19 | 2/8/19 | No Mod Req. | 2/13/19 | Bridgeport | 505.2.3 | Section 505.2.3, of the 2015 International Building Code portion of the 2018 State Building Code which sets forth requirements for “Mezzanines.” | |
M-0089-19 | 2/6/19 | APPROVED | 2/11/19 | 11 Oldfield Drive | Fairfield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0088-19 | 2/6/19 | APPROVED | 2/11/19 | 18 Horseshoe Drive | Danbury | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that "The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm)." |
M-0087-19 | 2/6/19 | APPROVED | 2/7/19 | Litchfield | 403.2 | Section 403.2, of the 2015 International Plumbing Code portion of the 2018 State Building Code, which states in part that “Where plumbing fixtures are required, separate facilities shall be provided for each sex”. | |
M-0086-19 | 2/5/19 | APPROVED | 2/6/19 | Southington | 403.1 | Section 403.1, of the 2012 International Plumbing Code portion of the 2016 State Building Code, which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 403.1”(drink fountain required). | |
M-0085-19 | 2/5/19 | APPROVED | 2/6/29 | Niantic | N1103.6 | Section N1103.6 of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that "Heating and Cooling equipment shall be sized based on the building loads. | |
M-0084-19 | 2/4/19 | No Mod Req. | 2/6/19 | 7 Wright Lane | Hamden | R311.7.1 | Section R311.7.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The width of existing stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall not be less than 32 inches in clear width at all points above the permitted handrail height and below the required headroom height. |
M-0083-19C | 2/4/19 | APPROVED | 2/5/19 | 164 Juniper Drive | Avon | R311.7.2(2) | Section R311.7.2(2), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 4 inches”. |
M-0083-19B | 2/4/19 | APPROVED | 2/5/19 | 164 Juniper Drive | Avon | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0083-19A | 2/4/19 | APPROVED | 2/5/19 | 164 Juniper Drive | Avon | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the “building thermal envelope” |
M-0082-19 | 2/4/19 | APPROVED | 2/5/19 | 1 Linde Street | West Haven | R324.7.2.2 | Section R324.7.2.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for “Access Pathway on roofs where solar photovoltaic array are installed”. |
M-0081-19C | 2/4/19 | APPROVED | 2/5/19 | 132 Mimosa Circle | Ridgefield | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0081-19B | 2/4/19 | APPROVED | 2/5/19 | 132 Mimosa Circle | Ridgefield | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the “building thermal envelope” |
M-0081-19A | 2/4/19 | APPROVED | 2/5/19 | 132 Mimosa Circle | Ridgefield | R302.11 | Section R302.11, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for “fire blocking”. |
M-0080-19D | 2/4/19 | DENIED | 2/7/19 | Greenwich Library 101 West Putnam Avenue |
Greenwich | 712.1.3.1 | Section 712.1.3.1, of the 2012 International Building portion of the 2016 State Building Code, which states in part that “An Escalator’s protection by a draft curtain and closely spaced sprinklers in accordance with NFPA 13 shall be permitted where the area of the vertical opening between stories does not exceed twice the horizontal projected area of the escalator. In other than Groups B and M, this application is limited to openings that do not connect more than four stories”. |
M-0080-19C | 2/4/19 | DENIED | 2/7/19 | Greenwich Library 101 West Putnam Avenue |
Greenwich | 712.1.3.1 | Section 712.1.3.1, of the 2012 International Building portion of the 2016 State Building Code, which states in part that “An Escalator’s protection by a draft curtain and closely spaced sprinklers in accordance with NFPA 13 shall be permitted where the area of the vertical opening between stories does not exceed twice the horizontal projected area of the escalator. In other than Groups B and M, this application is limited to openings that do not connect more than four stories”. |
M-0080-19B | 2/4/19 | DENIED | 2/7/19 | Greenwich Library 101 West Putnam Avenue |
Greenwich | 712.1.3 | Section 712.1.3, of the 2012 International Building portion of the 2016 State Building Code, which states in part that “Escalator opening shall be protected according to Sections 712.1.3.1 or 712.1.3.2 of the above mentioned code”. |
M-0080-19A | 2/4/19 | APPROVED | 2/7/19 | Greenwich Library 101 West Putnam Avenue |
Greenwich | 2016SBC | Continued use of the 2016 State Building Code |
M-0079-19 | 2/4/19 | APPROVED | 2/5/19 | 220 Farmington Avenue | Farmington | Rule 2.7.4.1 Connecticut Safety Code for Elevators & Escalators | Rule 2.7.4.1, of the 2018 Connecticut Safety Code for Elevators and Escalators, which states in part that “Elevator machine rooms shall have a clear headroom of not less than 7 feet”. |
M-0078-19 | 2/4/19 | DENIED | 2/5/19 | 22 Pond Place | Cos Cob | R311.7.5 | Section R311.7.5, of the 2009 International Residential Code portion of the 2005 State Building Code, which states in part that “There shall be a landing at the top and bottom of each stairway”. |
M-0077-19 | 2/4/19 | APPROVED | 2/5/19 | 290 West Maion Street (Clipper Center) |
Avon | 334.12(A)(2) | “NM cables shall not be permitted to be exposed within a dropped or suspended ceiling cavity in other than one and two-family and multifamily dwellings”. |
M-0076-19 | 1/30/19 | APPROVED | 2/1/19 | 305 Spruce Bank Road | Hamden | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0075-19 | 1/30/19 | APPROVED | 2/1/19 | 62 Forest Drive | Newington | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0074-19 | 1/30/19 | APPROVED | 2/1/19 | 1635 King Street | Enfield | 2902.2 | Section 2902.2, of the 2012 International Building Code portion of the 2016 State Building Code which states in part that “Where plumbing fixtures are required, separate facilities shall be provided for each sex”. |
M-0073-19 | 1/18/19 | APPROVED | 2/1/19 | 191 Summer Street | Stamford | 2.22.2 (2018 SEC) | Section 2.22.2, of the 2013 Ed. of ASME A17.1. (Approved language of the 2018 State Elevator Code) |
M-0072-19 | 1/29/19 | APPROVED | 1/30/19 | 3 Princeton Lane | New Fairfield | 2016SBC | Continued use of the 2016 State Building Code |
M-0071-19 | 1/29/19 | APPROVED | 1/30/19 | 1 Country Farm Lane | New Milford | 2016SBC | Continued use of the 2016 State Building Code |
M-0070-19 | 1/29/19 | DENIED | 2/6/19 | 1 Pucci Park | New Britain | 240.21(13) | Section 240.21(13), of the 2017 National Electrical Code portion of the 2018 State Building Code, which states sets forth the requirements for “Feeder Taps”. |
M-0069-19 | 1/29/19 | DENIED | 2/13/19 | 1201 Boston Post Road | Milford | 907 | Section 907, of the 2012 International Building Code portion of the 2016 State Building Code, which sets forth requirements for “Emergency Voice/Alarm Communication Systems within malls”. |
M-0068-19 | 1/29/19 | APPROVED | 1/30/19 | 307 Manor Road | Southbury | 807.1 | Section 807.1, of the 2015 International Residential Code portion of the 2018State Building, which states in part that “In buildings with combustible ceiling or roof construction, an attic access opening shall be provided to attic areas that exceed 30 square feet and have a vertical height of 30 inches”. |
M-0067-19 | 1/29/19 | APPROVED | 1/30/19 | 311 Burr Hall | Middlebury | M1503.4 | Section M1503.4 of the 2012 International Residential Code portion of the 2016 State Building Code which states in part, “Exhaust hood systems capable of exhausting in excess of 400 cubic feet per minute (0.19 m3/s) shall be provided with makeup air at a rate approximately equal to the exhaust air rate.” |
M-0066-19 | 1/28/19 | APPROVED | 1/30/19 | 98 Grove Street | New Milford | 110.26(A) | Section 110.26(A), of the 2017 National Electrical Code portion of the 2018 State Building Code, which states in part that “Working space for equipment likely to require examination, servicing or maintenance while energized shall comply with the dimension of 110.26(A)(1), (A2) and (A3) indicated in Table 110.26(A)(1) (3 feet)”. |
M-0065-19 | 1/28/19 | DENIED | 1/29/19 | 169 Boston Post Road | Waterford | 2902.2 | Section 2902.2, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “where plumbing fixtures are required, separate facilities shall be provided for each sex”. |
M-0064-19 | 1/28/19 | APPROVED | 2/1/19 | 411 Welches Point Road | Milford | R101.2 | Section R101.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “the provisions of this code shall apply to the construction, alteration, repair, use and occupancy of detached one and two family dwellings not more than three stories in height”. |
M-0063-19 | 1/25/19 | DENIED | 1/29/19 | 339 Center Street | West Haven | R302.1 | Section R302.1, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The opening within exterior walls within 3 feet of a property line are not permitted”. |
M-0062-19 | 1/25/19 | APPROVED | 1/29/19 | 112 Spring Hill Avenue | Norwalk | R305.1(2) | The ceiling height above bathroom and toilet room fixtures shall be such that the fixture is capable of being used for its intended purpose. A shower or tub equipped with a shower head shall have a ceiling height of not less than 6 feet 8 inches (2032 mm) above an area of not less than 30 inches (762 mm) by 30 inches (762 mm) at the showerhead. |
M-0061-19 | 1/25/19 | APPROVED | 1/29/19 | Harbor Point Parcels, P1-P2-P3-P4-P5-P6 |
Stamford | 1106.2 | Section 1106.2, of the 2012 International Building Code portion of the 2016 State Building Code. |
M-0060-19 | 1/25/19 | APPROVED | 1/29/19 | 472 Hoyt Farm Road | New Canaan | 210.52(C)(1) | Section 210.52(C)(1), of the 2014 National Electrical Code portion of the 2016 State Building Code which states in part that “A receptacle outlet shall be installed at each wall counter space so that no point along the wall line is more than 24 inches from a receptacle outlet”. |
M-0059-19 | 1/25/19 | RETURNED for B.O. Signature | 1/29/19 | 14 Diamond Street | Naugatuck | 116.1 | Section 116.1, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “Structures or existing equipment that are or hereafter become unsafe, insanitary or deficient because of inadequate means of egress facilities, inadequate light and ventilation, or which constitute a fire hazard, or are otherwise dangerous to human life or the public welfare, or that involve illegal or improper occupancy or inadequate maintenance, shall be deemed an unsafe condition. Unsafe structures shall be taken down and removed or made safe, as the building official deems necessary…” |
M-0058-19 | 1/24/19 | APPROVED | 1/28/19 | 25 Canal Bank Road | Windsor Locks | 3006 | Section 3006, of the 2015 International Building Code portion of the 2018 State Building Code. |
M-0057-19 | 1/23/19 | APPROVED | 1/28/19 | 200 Linwood Street, New Britain | New Britain | R305.1(2) | The ceiling height above bathroom and toilet room fixtures shall be such that the fixture is capable of being used for its intended purpose. A shower or tub equipped with a shower head shall have a ceiling height of not less than 6 feet 8 inches (2032 mm) above an area of not less than 30 inches (762 mm) by 30 inches (762 mm) at the showerhead. |
M-0056-19 | 1/23/19 | APPROVED | 1/24/19 | 37 Rosedale Road | West Hartford | R311.7.1 | Section R311.7.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The width of existing stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall not be less than 32 inches in clear width at all points above the permitted handrail height and below the required headroom height. |
M-0055-19 | 1/23/19 | APPROVED | 1/24/19 | 151 Raynor Street | Southington | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the “building thermal envelope” |
M-0054-19 | 1/23/19 | APPROVED | 1/24/19 | 33 Wooster Heights | Danbury | R305.1(2) | The ceiling height above bathroom and toilet room fixtures shall be such that the fixture is capable of being used for its intended purpose. A shower or tub equipped with a shower head shall have a ceiling height of not less than 6 feet 8 inches (2032 mm) above an area of not less than 30 inches (762 mm) by 30 inches (762 mm) at the showerhead. |
M-0053-19 | 1/22/19 | on hold w/Deputy | 194 South Avenue | New Canaan | on hold w/Deputy | ||
M-0052-19 | 1/22/19 | APPROVED | 2/5/19 | 611 Norwich Avenue | Taftville | 306.1 | Section 306.1, of the 2003 International Mechanical Code Portion of the 2005 State Building Code, which sets forth requirements for “access to mechanical equipment”. |
M-0051-19 | 1/22/19 | APPROVED | 1/24/19 | 284 Umpawaug Road | Redding | N1103.2.2 | Section N1103.2.2, of the 2009 International Residential Code portion of the 2005 State Building Code, which requires leakage test be performed on ductwork. |
M-0050-19 | 1/22/19 | APPROVED | 1/24/19 | 115 Upland Road | New Milford | P2705.1(5) | Section P2705.1(5), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “there shall be a minimum of 15 inches from the center of a water closet to a vanity”. |
M-0049-19 | 1/16/19 | APPROVED | 1/23/19 | Oxford Middle School Great Oak Road |
Oxford | 403.1 | Section 403.1, of the 2015 International Plumbing Code portion of the 2018 State Building Code, which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 403.1”. |
M-0048-19 | 1/16/19 | APPROVED | 1/23/19 | 326 Georgetown Road | Weston | 312.1.1.1 | Section R312.1.1.1, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “Retaining walls with a difference in finished grade from the top of the wall to the bottom of the wall that is greater than 4 feet (1219 mm) shall be provided with guards complying with Section R312 when there is a walking surface, parking lot or driveway on the high side located closer than 2 feet (610 mm) to the retaining wall”. |
M-0047-19 | 1/16/19 | APPROVED | 1/17/19 | 52 Indianola Road | Niantic | R301.2.1.2 | Section R301.2.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “wood structural panels with a minimum thickness of 7/16 inch and a maximum span of 8 feet shall be permitted for opening protection in one- and two-story buildings. Panels shall be precut and attached to the framing surrounding the opening containing the product with the glazed opening. Panels shall be predrilled as required for the anchorage method and shall be secured with the attachment hardware provided”. |
M-0046-19B | 1/16/19 | DENIED | 1/17/19 | 145 Dorrance Street | Hamden | R311.7.2 | Section R311.7.2(2), of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 4 inches”. |
M-0046-19A | 1/16/19 | APPROVED/DENIED | 1/17/19 | 145 Dorrance Street | Hamden | R305.1.1(4) | Section R305.1.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 10 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0045-19 | 1/16/19 | APPROVED | 1/17/19 | 57 Nehantic Road | Niantic | R301.2.1.2 | Section R301.2.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that wood structural panels with a minimum thickness of 7/16 inch and a maximum span of 8 feet shall be permitted for opening protection in one- and two-story buildings. Panels shall be precut and attached to the framing surrounding the opening containing the product with the glazed opening. Panels shall be predrilled as required for the anchorage method and shall be secured with the attachment hardware provided. |
M-0044-19 | 1/16/19 | APPROVED | 1/17/19 | 616 Goodale Hill Road | Glastonbury | R305.1(2) | The ceiling height above bathroom and toilet room fixtures shall be such that the fixture is capable of being used for its intended purpose. A shower or tub equipped with a shower head shall have a ceiling height of not less than 6 feet 8 inches (2032 mm) above an area of not less than 30 inches (762 mm) by 30 inches (762 mm) at the showerhead. |
M-0043-19 | 1/14/19 | APPROVED | 1/17/19 | 200 Tyler Street | East Haven | 706.2 | Section 706.2, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Fire walls shall be designed and constructed to allow collapse of construction on either side without collapse of the wall under fire conditions.” |
M-0042-19 | 1/14/19 | APPROVED | 1/15/19 | Russell Hall 110 North Eaglesville Road |
Storrs | 1014.11 | Section 1014.11, of the BOCA National Building Code 1996 portion of the 1994 State Building, which states in part that “penetrations into and openings through an exit enclosure assembly are prohibited except for required exit doors”. |
M-0041-19 | 1/14/19 | APPROVED | 1/15/19 | 1616 Mapleton Avenue | Suffield | 403.1 | Section 403.1, of the 2015 International Plumbing Code portion of the 2018 State Building Code, which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 403.1”. |
M-0040-19 | 1/14/19 | APPROVED | 1/15/19 | 110 North Eaglesville Road | Storrs | 1014.11 | Section 1014.11, of the BOCA National Building Code 1996 portion of the 1994 State Building, which states in part that “penetrations into and openings through an exit enclosure assembly are prohibited except for required exit doors”. |
M-0039-19 | 1/11/19 | APPROVED | 1/15/19 | 100 N. Water Street | Norwalk | 2902.5 and 2902.6 | Sections 2902.5 and 2902.6, of the 2003 International Building Code portion of the 2005 State Building Code, which requires both employee and public toilet facilities to be located not more than one story above or below the space required to have toilet facilities. |
M-0038-19 | 1/11/19 | APPROVED | 1/15/19 | 135 Chestnut Ridge Road | Bethel | P2705.1(5) | Section P2705.1(5), of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “there shall be a minimum of 15 inches from the center of a lavatory wall”. |
M-0037-19 | 1/11/19 | APPROVED | 1/15/19 | 1 Devon Road | Darien | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0036-19 | 1/11/19 | APPROVED | 1/15/19 | 37 Hart Circle | Waterbury | 240.24(E) | Section 240.24(E), of the 2017 National Electrical Code portion of the 2018 State Building Code, which states in part that “Overcurrent devices shall not be located in bathrooms”. |
M-0035-19 | 1/11/19 | APPROVED | 1/15/19 | 25 Ridge Lane | Wilton | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0034-19 | 1/11/19 | APPROVED | 1/15/19 | 1 Greenwich Plaza | Greenwich | 110.26(E)(1)(a) | Section 110.26(E)(1)(a), of the 2014 National Electrical Code portion of the 2016 State Building Code, which states in part that “No piping, ducts, leak protection apparatus or other equipment foreign to the electrical installation shall be located within the required dedicated electrical space”. |
M-0033-19 | 1/11/19 | APPROVED | 1/15/19 | 15 Clew Drive | Middletown | 2016SBC | Continued use of the 2016 State Building Code |
M-0032-19 | 1/11/19 | APPROVED | 1/15/19 | 37 Briarwood Drive | East Hartford | 310.2.2 | Section 310.2.2, of the 2015 International Residential portion of the 2018 State Building Code, which states in part that “where windows are provided as the emergency escape and rescue opening, they shall have a sill height of not less than 44 inches above the floor”. |
M-0031-19B | 1/11/19 | APPROVED | 1/15/19 | 16 Olmsted Street | East Hartford | 1809.5 | Section 1809.5, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “Except where otherwise protected from frost, foundation walls, piers or other permanent supports for buildings and structures shall extend below the established frost line (42 inches)”. |
M-0031-19A | 1/11/19 | APPROVED | 1/15/19 | 16 Olmsted Street | East Hartford | 1011.5.2 and 1011.5.4 | Sections 1011.5.2 and 1011.5.4, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “Stair riser heights shall be 7 inches maximum and the tolerance between the largest and smallest riser height shall not exceed 3/8 of an inch”. |
M-0030-19 | 1/11/19 | APPROVED | 1/15/19 | 107 Olmsted Street | East Hartford | R403.1.4.1 | Section R403.1.4.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Except where otherwise protected from frost, foundation walls, piers or other permanent supports for buildings and structures shall extend below the established frost line (42 inches)”. |
M-0029-19 | 1/10/19 | APPROVED | 1/11/19 | ESCU-Shafer Hall 80 High Street |
Willimantic | 210.52(2)(1) - (2014 NEC/2016SBC) | Section 210.52(A)(1) and (A)(2), of the 2014 National Electrical Code portion of the 2016 State Building Code, which sets forth requirements for the "location of receptacle outlets within residential occupancies". |
M-0028-19 | 1/10/19 | APPROVED | 1/11/19 | 815 Still Hill Road | Hamden | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0027-19B | 1/10/19 | APPROVED | 1/11/19 | 225 Pond View Drive | Southington | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the building “thermal envelope”. |
M-0027-19A | 1/10/19 | APPROVED | 1/11/19 | 225 Pond View Drive | Southington | R305.1(4) | Section R305.1(4), of the 2015 International Residential Code portion of the 2018 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 8 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0026-19 | 1/10/19 | APPROVED | 1/11/19 | 2 Broadway #6 | North Haven | 403.3.1.1 | Section 403.3.1.1, of the 2015 International Mechanical Code portion of the 2018 State Building Code, which sets forth requirements for “source capture systems in nail salons”. |
M-0025-19 | 1/10/19 | APPROVED | 1/11/19 | Edward V. Grant Science Complex 2152 Hillside Road |
Storrs | 404.2.3.2 | Section 404.2.3.2, of the 2009 ICC A117.1 portion of the 2018 State Building Code. |
M-0024-19 | 1/9/19 | APPROVED | 1/11/19 | 445 Eastern Point Road | Groton | 1008.1.9.9 | Section 1008.1.9.9, of the 2012 International Building Code portion of the 2016 State Building Code, which “prohibits the use of electromagnetically locked doors within Group F Occupancy’s”. |
M-0023-19 | 1/9/19 | DENIED | 1/14/19 | 2399 Main Street | Stratford | 1010.3 | Section 1010.3, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “Ramps used in other than a means of egress shall have a slope not greater than one unit vertical in eight units horizontal. The slope of other pedestrian ramps shall not be steeper than one unit vertical in eight units horizontal”. |
M-0022-19 | 1/9/19 | APPROVED | 1/11/19 | 237 Hickok Road | New Canaan | R305.1.1(2) | Section R305.1.1(2), of the 2012 International Residential Code portion of the 2016 State Building Code, which states that “The ceiling height in existing basements being converted to habitable space shall not be less than 6 feet, 10 inches clear except for under beams, girders, ducts or other obstructions where the clear height shall be a minimum of 6 feet, 4 inches”. |
M-0021-19 | 1/9/19 | APPROVED | 1/15/19 | 20 York Street (YALE) | New Haven | 1014.2 | Section 1014.2, of the 2015 International Building Code portion of the 2018 State Building Code, which states in part that “the height of handrails shall be not less than 34 inches and not more than 38 inches measured above the stair tread nosing. |
M-0020-19 | 1/9/19 | APPROVED | 3/18/19 | REVISED 1111 Country Club Road |
Middletown | 503.2.1 | Section 503.2.1, of the 2009 International Energy Conservation Code portion of the 2005 State Building Code, which states in part that “Output capacity of heating and cooling equipment and systems shall not exceed the loads calculated in accordance with Section 503.2.1”. |
M-0019-19 | 1/9/19 | APPROVED | 1/11/19 | 68 Blackwood Lane | Stamford | R305.1 | Section R305.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “Habitable rooms and hallways shall have a ceiling height of not less than 7 feet”. |
M-0018-19 | 1/8/19 | APPROVED | 1/11/19 | 261 Sharon Road | Lakeville | 2902.1 | Section 2902.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 2902.1.” |
M-0017-19 | 1/8/19 | APPROVED | 1/11/19 | 11 Interlaken Road | Lakeville | 2902.1 | Section 2902.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 2902.1.” |
M-0016-19 | 1/8/19 | APPROVED | 1/11/19 | 283 North Washington Street | Plainville | 2016SBC | Continued use of the 2016 State Building Code |
M-0015-19 | 1/8/19 | APPROVED | 1/11/19 | 687 East Broadway | Milford | R101.2 | Section R101.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The provisions of this Code shall apply to the construction, alteration, repair, use and occupancy of detached one and two family dwellings not more than three stories in height”. |
M-0014-19B | 1/8/19 | APPROVED | 2/1/19 | 25 Ridgefield Street Dr. Martin Luther King, Jr. Campus |
Hartford | 1004.1.1.1 | Section 1004.1.1.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Where occupants egress from one area or space through others, the design occupant load shall be combined occupant load of interconnected accessory or intervening spaces.” |
M-0014-19A | 1/8/19 | No Mod Req. | 2/1/19 | 25 Ridgefield Street Dr. Martin Luther King, Jr. Campus |
Hartford | 2902.1 | Section 2902.1, of the 2015 International Building Code portion of the 2018 State Building Code which states in part that “Plumbing fixtures shall be provided for the type of occupancy and in the minimum numbers shown in Table 2902.1.” |
M-0013-19B | 1/7/19 | APPROVED | 1/10/19 | 155 Firetown Road | Simsbury | 402.1 (2015 IEBC) (2018 SBC) | Section 402.1, of the 2015 International Existing Building Code portion of the 2018 State Building Code which states in part that “An existing building plus additions shall comply with the height and area requirements of Chapter 5 of the International Building Code”. |
M-0013-19A | 1/7/19 | APPROVED | 1/10/19 | 155 Firetown Road | Simsbury | 402.1 (2015 IEBC) (2018 SBC) | Section R311.7.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 4 inches”. |
M-0012-19 | 1/7/19 | APPROVED | 1/9/19 | 19 Fairview Road | Brookfield | N1102.1.2 | Section N1102.1.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which sets forth requirements for the “building thermal envelope” |
M-0011-19 | 1/7/19 | APPROVED | 1/9/19 | 855 Hill Street | Hamden | R305.1(4) | Ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm). |
M-0010-19B | 1/7/19 | APPROVED | 1/9/19 | 11 Webber Road | Rocky Hill | R311.7.1 | Section R311.7.1, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The width of existing stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall not be less than 32 inches in clear width at all points above the permitted handrail height and below the required headroom height. |
M-0010-19A | 1/7/19 | APPROVED | 1/9/19 | 11 Webber Road | Rocky Hill | R311.7.2 | Section R311.7.2, of the 2015 International Residential Code portion of the 2018 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 4 inches”. |
M-0009-19 | 1/7/19 | APPROVED | 1/9/19 | 48 Beech Road | Enfield | R305.1(4) | Ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm). |
M-0008-19 | 1/7/19 | DENIED | 1/9/19 | 132 Deepwood Drive | Manchester | R311.7.2 | Section R311.5.2, of the 2012 International Residential Code portion of the 2016 State Building Code, which states in part that “The minimum headroom in all parts of existing or replacement stairways serving existing unfinished attics or existing unfinished basements being converted to habitable space shall be 6 feet, 6 inches”. |
M-0007-19 | 1/7/19 | APPROVED | 1/11/19 | 195 West Thames Street | Norwich | 1009.9.2 | Section 1009.9.2, of the 2012 International Building Code portion of the 2016 State Building Code which states in part that “Exterior stairways in climates subject to snow and ice shall be protected to prevent the accumulation of same”. |
M-0006-19 | 1/7/19 | APPROVED | 1/9/19 | 600 Orange Avenue | Milford | 2016SBC | Continued use of the 2016 State Building Code |
M-0005-19 | 1/2/19 | APPROVED | 1/9/19 | 13 West Main Street | Niantic | 1208.2 | Section 1208.2, of the 2012 International Building Code portion of the 2016 State Building Code, which states in part that “Occupiable spaces shall have a ceiling height of not less than 7 feet, 6 inches”. |
M-0004-19 | 1/2/19 | APPROVED | 1/9/19 | 240 Ball Pond Road | New Fairfield | 2016SBC | Continued use of the 2016 State Building Code |
M-0003-19 | 1/2/19 | APPROVED | 1/9/19 | 220 New Britain Avenue | Plainville | 2016SBC | “At least one receptacle outlet shall be installed at each island counter space with a long dimension of 24 inches or greater and a short dimension of 12 inches or greater”. |
M-0002-19 | 1/2/19 | APPROVED | 1/9/19 | 3 Pelham Road | West Hartford | M1503.4 | Section M1503.4 of the 2015 International Residential Code portion of the 2018 State Building Code which states in part, “Exhaust hood systems capable of exhausting in excess of 400 cubic feet per minute (0.19 m3/s) shall be provided with makeup air at a rate approximately equal to the exhaust air rate.” |
M-0001-19 | 1/2/19 | APPROVED | 1/9/19 | 34 Higgins Avenue | Plainville | R305.1(4) | Ceiling height in existing basements being converted to habitable space shall not be less than 6 feet 8 inches (2032 mm) clear except under beams, girders, pipes, ducts or other obstructions where the clear height shall be a minimum of 6 feet 4 inches (1931 mm). |